Cutting water consumption by 43% at a large mixed-use facility

Two workers in an excavation beside a large steel water main fitted with a flow meter

CASE STUDY · WATER LOSS REDUCTION

By Kendall Slater, Pr Eng · JOAT Consulting · October 2026

Summary

JOAT reduced water consumption at a large mixed-use facility by about 43%, saving around 5 000 kℓ of water a day. The saving came from dividing the network into monitored zones, finding and repairing hidden leaks with FIDO AI acoustic leak detection, and managing pressure with pressure-reducing valves (PRVs).

The challenge: one bulk meter, many unknowns

The facility is home to a mix of residential, institutional and recreational users. Each has a different water-use pattern, and all are supplied through a single bulk meter feeding a large, complex internal network.

With only the bulk meter in place, the owner could see how much water entered the site but not where it went. JOAT’s analysis of the population and water-use profiles indicated that a large share of the water being paid for was being lost rather than used.

Starting with a credible baseline

Savings are only as credible as the baseline they are measured against. JOAT analysed 18 months of billing data. Because the bills included estimated readings and anomalies, the data was normalised and a baseline was agreed with the client before work began.

An agreed baseline protects both parties: the client knows the savings are real, and the savings can be verified independently of who did the work.

What JOAT did

1. Divide the network and measure it. Flow meters were installed at critical points, and the site was divided into smaller District Metered Areas (DMAs) and Pressure Managed Zones (PMZs), each with a confirmed, single point of supply.

2. Find and fix hidden leaks. Once each zone could be measured, JOAT used the flow data to target the zones losing the most water. Field teams then combined visual inspections, on-site investigations and FIDO AI acoustic leak detection to locate and prioritise leaks, most of which were not visible at the surface.

3. Manage pressure. Where zones were running at higher pressure than consumers needed, JOAT commissioned pressure-reducing valves. Lower pressure reduces the flow through every remaining leak and lowers the risk of new bursts.

4. Monitor and verify. Flow in every zone is monitored continuously, so the effect of each repair and each PRV can be seen in the data and verified against the baseline.

The results

Measured at the bulk meter, consumption has fallen by about 43% against the agreed baseline: a saving of around 5 000 kℓ of water a day.

Bar chart of bulk meter consumption: 100% at the agreed baseline and about 57% in October 2026, a reduction of about 43%

Figure 1: Bulk meter consumption as a percentage of the agreed baseline

Results at zone level

  • Recreational area: leak repairs combined with pressure management more than halved the supply, from about 4,5 kℓ/h to just over 2 kℓ/h.

  • Large residential zone: repairing a major leak, then commissioning a PRV, reduced average flow from about 90 kℓ/h to about 75 kℓ/h. Both steps show as distinct drops in the flow data.

What 5 000 kℓ a day means

  • Enough to fill two Olympic swimming pools every day (about 2 500 kℓ each).

  • Roughly the daily use of 10 000 households, at 500 litres per household per day.

  • About 1,8 million kℓ a year: water no longer bought, treated and pumped only to be lost.

Five lessons for owners of large sites

  1. Agree the baseline first. Savings must be measured against a number everyone accepts.

  2. Zone the network. A single bulk meter tells you how much you lose, not where.

  3. Combine methods. Flow data shows which zone is losing water; acoustic detection shows where in the zone.

  4. Manage pressure. It reduces losses even from leaks that have not been found yet.

  5. Fund the work from the savings. In a shared-savings model, the provider’s fee is linked to verified savings, so the client avoids a large up-front cost.

Frequently asked questions

What causes high water consumption at large sites? Usually a combination of hidden underground leaks, excess network pressure, leaking fittings in buildings and inaccurate or estimated billing. On large sites with ageing internal networks, losses can make up a significant share of the water purchased.

What is a District Metered Area (DMA)? A section of a water network with a defined boundary and metered inlets, so the water entering it can be measured and compared with expected use.

What is a shared-savings water contract? A contract in which the service provider is paid from the verified savings it delivers, measured against an agreed baseline. The client pays little or nothing up front, and the provider carries the performance risk.

Does this approach work for other large sites? Yes. It applies to any site supplied through a bulk meter with its own internal network, including campuses, hospitals, industrial parks, residential estates and municipal supply zones.

About the author

Kendall Slater, Pr Eng, JOAT Consulting

Kendall Slater, Pr Eng

Kendall is a registered professional engineer at JOAT Consulting, working on water loss reduction projects for municipalities and large facilities.

LEAK DETECTION TECHNOLOGY · FIDO AI, distributed locally by JOAT

FIDO logo

Talk to JOAT

Is your site paying for water it never uses? JOAT can assess your consumption, agree a baseline and propose a shared-savings programme.

sales@joat.co.za · +27 31 700 1177 · www.joat.co.za